Earth Resistivity and Resistance Tester

SKU: K4106

  • High test current up to 80mA yielding resolution of 0.001Ω on 2Ω range.
  • Advanced Filtering method (based on FFT Fast Fourier Transform) reduces noise interference for obtaining stable measurements.
  • Earth resistance measurement with 4, 3 and 2 wires
  • Earth resistivity tester (ρ) using 4 pole Wenner method
  • 800 Data storage points
  • Test current frequency in four bands of 94 / 105 / 111 / 128Hz
  • Earth (Ground) Resistance 200kΩ
  • Earth Soil Resistivity 200kΩ
  • “Zero adjust” the Residual Resistance (Rk)
  • Soil Earth Resistivity is automatically calculated
  • Distance set within a range of 1.0 to 30.0m at 0.1m steps
  • Several sub-results and parameters can be shown on the display: Resistance of the Auxiliary Earth Spikes, Frequency of Test Current, Voltage and Frequency of Interference (noise), Residual Resistance Rk, etc.
  • Memory, recall and download - results via USB adaptor
  • Warning indication of noise & high resistance of auxiliary earth spikes
  • Robust design with IP54 protection.
  • CAT II 600V and CAT III 300V 

R 39 500.00 ex. VAT R 45 425.00 in. VAT

Details

The K4106 is a 2/3/4-wire Digital Earth resistance/Earth Resistivity Tester equipped with a microcomputer and can measure earth resistances and calculate earth resistivity’s (ρ), using the “Wenner” 4 pole method. This instrument is ideal for Earth measurements also in large Earthing systems because it uses a considerable test current of 80mA(max) yielding a high resolution of 1mΩ on 2Ω range. The Earth Resistivity measurement is useful for soil surveys to establish the optimum earth electrode system design and site, to avoid extra cost of reworking electrode installations. It can also be suitable for geological investigations.

Specifications:

Function

Range

Resolution

Measuring range

Accuracy

Earth resistance Re
(Rg at ρ measurement)

0.001Ω

0.03 to 2.099Ω

±(2%rdg±0.03Ω)

20Ω

0.01Ω

0.03 to 20.99Ω

± (2%rdg±5dgt (*1))

200Ω

0.1Ω

0.3 to 209.9Ω

2000Ω

3 to 2099Ω

20kΩ

10Ω

0.03 to 20.99kΩ

200kΩ

100Ω

0.3 to 209.9kΩ

Auxiliary earth resistance Rh, Rs

 

 

 

(8% of Re+Rh+Rs)

Earth resistivity ρ

0.1 to 1Ω·m
Auto-ranging

0.2 to 395.6Ω·m

(ρ=2×π×a×Rg (*2))

20Ω

0.2 to 3956Ω·m

200Ω

20 to 39.56kΩ·m

2000Ω

0.2 to 395.6kΩ·m

20kΩ

2.0 to 1999kΩ·m

200kΩ

Series interference voltage Ust (A.C only) (*3)

50V

0.1V

0 to 50.9Vrms

± (2%rdg ± 2dgt (50/60Hz))

± (3% rdg ± 2dgt (40 to 500Hz))

Frequency Fst

Auto-ranging

0.1Hz
1Hz

40Hz to 499.9Hz

± (1% rdg ± 2 dgt)

Measuring method

Earth resistance: Fall-of-potential method
(currents and voltages measured via the Probes)
Measurement method of Earth Resistivity (ρ): Wenner 4-pole method
Series interference voltage (earth voltage)
RMS Rectifier (between the E-S Terminals)

Memory capacity

800 data

Communication Interface

PC Intgerface

Display

LCD Display

Over-range Indication

Yes

Overload Protection

between E-S(P) and between E-H(C) terminals AC280V / 10 sec.

Power source

R6 × 8
(Auto power off: Approx. 5 minutes)

Dimension

167(L) × 185(W) × 89(D) mm

Weight

Approx. 900g (including batteries)

Safety Specs

IEC 61010 – CAT II 600V and CAT III 300V

Safety Rating

Warranty

Accessories:

  • K7229A (Earth precision measurement)
  • K7238A (Simplified measurement test leads)
  • K8032 (Auxiliary earth spikes [2 spiks/set]) ×2 sets (4 spikes in total)
  • K8200-04 (Cord reel [4 pcs]) ×1 set
  • K8212-USB (USB adaptor with "KEW Report(Software)
  • K9121 (Shoulder strap)
  • K9125 (Carrying case)
  • R6 × 8
  • Instruction manual
  • Calibration certificate